Wall luminaire for escape route illumination. Base: die-cast aluminium, powder-coated Cover: polycarbonate. With plastic lenses for escape route illumination. Vertical swivel. Driver integrated. Suitable for connection to central battery systems. Luminaire with limited surface temperature in accordance with EN 60598-2-24 for use in environments in which a deposit of conductive dust on the luminaire can be expected.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Power circuit |
Battery | without |
Operating mode | maintained power mode |
Length L | 79 mm |
Width B | 198 mm |
Height H | 198 mm |
Weight | 0.78 kg |
Light source | LED |
Colour temperature | 6500 K |
Rated luminous flux, mains operation | 210 lm | 220 lm | 220 lm |
System power, mains operation | 2,9 W | 2,9 W | 2,9 W |
Rated luminous flux, emergency operation | 210 lm | 220 lm | 220 lm |
Beam angle |
down 69°/75°/14°/75° | 70°/77°/13°/77° | 76°/77°/6°/77° up 90°/90°/0°/90° | 90°/88°/0°/88° |
Rated life | 70000 h |
Colour rendering index (CRI) | 70 |
Driver | Electronic ballast |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 Hz, 60 Hz |
Luminaires on B10A fuse | 18 |
Luminaires on B16A fuse | 29 |
Luminaires on C10A fuse | 36 |
Luminaires on C16A fuse | 58 |
Inrush current / Inrush current duration | 3.3 A / 400 µs |
CIE Flux Code / CEN Flux Code | 30 58 90 93 100 |
Type of protection | IP 65 |
Protection class | I |
Filament test | 850 °C |
Impact resistance | IK08 |
Ambient temperature for maintained power | -20 °C ... + 40 °C |
Ambient temperature for non-maintained power mode | -20 °C ... + 40 °C |
Safety marks | D-mark |
Conformity mark | CE |