Flexible square surface-mounted multifunction downlight. Luminaire for escape route illumination. Housing: die-cast aluminium, powder-coated. Light guide and diffuser made of non-yellowing PMMA, opal matt. Suitable for Ceiling mounting, Wall (surface). Electronic ballast included. Self-contained system with automatic self-test and feedback to the RZB monitoring system MULTIDIGIT.
Technical Specifications
Typ of emergency lighting | Self-contained system |
---|---|
Monitoring | MultiDigit |
Battery | LiFePO4 |
Duration | 8 h |
Operating mode | maintained power mode |
Length L | 230 mm |
Width B | 230 mm |
Height H | 70 mm |
Weight | 1.75 kg |
Light source | LED |
Colour temperature | 3000 K | 4000 K |
Rated luminous flux, mains operation | 1050 lm | 1350 lm | 1900 lm | 2100 lm |
System power, mains operation | 11 W | 13 W | 16 W | 18 W |
Rated luminous flux, emergency operation | 180 lm |
System efficiency | 95 lm/W | 104 lm/W | 117 lm/W | 119 lm/W |
Glare evaluation RUG (4H 8H) | 24,5 | 25,4 | 26,6 | 27 |
Beam angle | 112° |
Rated life | 50000 h |
Colour rendering index (CRI) | 80 |
Photobiological safety according to EN 62471 | Risk group 1 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 50 Hz, 60 Hz |
Luminaires on B10A fuse | 33 |
Luminaires on B16A fuse | 54 |
Luminaires on C10A fuse | 56 |
Luminaires on C16A fuse | 90 |
Inrush current / Inrush current duration | 13 A / 168 µs |
CIE Flux Code / CEN Flux Code | 47 79 96 100 100 |
Type of protection | IP 40 |
Protection class | I |
Filament test | 650 °C |
Impact resistance | IK03 |
Ambient temperature for maintained power | 5 °C ... + 30 °C |
Ambient temperature for non-maintained power mode | 5 °C ... + 30 °C |
Conformity mark | CE, EAC |
Downloads
Light Calculator
The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.