High quality recessed downlight.. Mounting bracket: galvanised sheet steel. Inner ring and square cover plate: die-cast aluminium. Brilliantly luminous corona at the light-emitting surfaces thanks to use of a specially designed cast aluminium ring as a reflector closure.. Reflector material: MIRO-SILVER® with 98 percent total light reflection. Patented round design shaped like a truncated cone. MultiLumen: 16 different luminous fluxes can be set on site in approx. 200 lm steps using DIP switches on the separate converter. Installation without tools thanks to spring fastening system. Suitable for through wiring as standard. Through-wiring box (5 pole) available as accessory.
Technical Specifications
Length L | 242 mm |
---|---|
Width B | 242 mm |
Height H | 3 mm |
Cut-out diameter DA | 228 mm |
Luminaire: recess height HEL | 172 mm |
Ceiling thickness S | 6-35 mm |
Installation space length LE | 340 mm |
Installation space width BE | 540 mm |
Installation space height HE | 175 mm |
Weight | 1.29 kg |
Light source | LED |
Colour temperature | 3000 K |
Rated luminous flux | 1600 lm | 2500 lm | 3350 lm | 4750 lm |
System power | 11 W | 19 W | 26 W | 39 W |
System efficiency | 122 lm/W | 129 lm/W | 132 lm/W | 145 lm/W |
Glare evaluation RUG (4H 8H) | 27,9 | 29,5 | 30,5 | 31,7 |
Beam angle | 50°/31°/0°/31° |
Rated life | 50000 h (L90/B50) |
Colour rendering index (CRI) | 92 |
Colour tolerance (McAdam) | 2 SDCM |
Photobiological safety according to EN 62471 | Risk group 1 |
Driver | Converter, dimmable |
Control | DALI |
Voltage | 220 - 240 V / 50 Hz, 60 Hz |
Luminaires on B10A fuse | 18 |
Luminaires on B16A fuse | 30 |
Luminaires on C10A fuse | 23 |
Luminaires on C16A fuse | 36 |
Inrush current / Inrush current duration | 50 A / 10 µs |
CIE Flux Code / CEN Flux Code | 74 99 100 100 100 |
Type of protection | IP 20 |
Protection class | II |
Filament test | 850 °C |
Impact resistance | IK03 |
Ambient temperature | -20 °C bis + 25 °C |
Safety marks | Do not cover the recessed luminaire! |
Conformity mark | CE , EAC |
Downloads
Light Calculator
The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.