3-phase network monitoring module with test function. Suitable for installation in systems complying with DIN VDE 0108. For installation in sub distribution boards for detecting undervoltage and power failures in single-phase or three-phase power systems. Construction width: 18 mm. With test function and status LED for each input phase.
Technical Specifications
Type of Installation | DIN profile track |
---|---|
Input voltage | 230/400 V, 48 - 63 Hz |
Power rating | 5 VA |
Operate value | 0.85 x rated voltage |
Contact set | 1 x isolated changeover relay |
Display |
Green LED L1 ON/OFF: Visualization for voltage L1-N Green LED L2 ON/OFF: Visualization for voltage L2-N Green LED L3 ON/OFF: Visualization for voltage L3-N Yellow LED ON/OFF: Position of the output relay |
Terminal blocks (infeed) | 2.5 mm² |
Switching power | 1250 VA |
Network monitoring function | Yes |
Type of protection | IP 20 |
Protection class | II |
Length L | 87 mm |
Width B | 18 mm |
Height H | 65 mm |
Weight | 72 g |
Conformity mark | EAC |