E-Switch

981352.002

Modules and components, white

Electronic changeover switch for installation in luminaires. Using the changeover switch, general lighting luminaires can be connected to emergency lighting and operated, provided that they are structurally suited for this. In this situation, the E-Switch is connected simultaneously to the mains supply of the general lighting and the mains supply of the emergency lighting. The emergency lighting mains supply always takes precedence here. In case of a power failure, this ensures that the luminaire also switches on even when the general lighting is switched off.

Technical Specifications

Type of Installation recessed mounting
Input voltage 207-253 V AC, 176-264 V DC
Switching time 100 ms
Switching power 250 VA
Switch entrance
Network monitoring function
Length L 82 mm
Width B 30 mm
Height H 21 mm
Weight 47 g
Type of protection IP 20
Protection class II
Conformity mark CE