Attractive cylindrical bollard with innovative housing design and high-quality LED optics. For escape route illumination. Luminaire tube Ø 115 mm made of corrosion-resistant aluminium profile, powder coated. Recessed stainless steel fixing plate. Non-corrosive gear compartment made of mould-cast dual compound thermoplastic with integral TP gasket. With membrane valve to avoid condensation. Luminaire head made of corrosion-resistant pressure die-cast aluminium, powder-coated, with clear glass cylinder and conical reflector. Connection box on base, max. 2 x 3 x 2.5 mm² for through wiring.Driver integrated. For connection to the emergency power supply.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Power circuit |
Battery | without |
Operating mode | maintained power mode |
Diameter D | 115 mm |
Height H | 1035 mm |
Weight | 5.34 kg |
Light source | LED |
Colour temperature | 3000 K |
Rated luminous flux, mains operation | 770 lm |
System power, mains operation | 10 W |
Rated luminous flux, emergency operation | 770 lm |
System power, emergency operation | 10 W |
System efficiency | 77 lm/W |
Glare evaluation UGR (4H 8H) | 23,7 |
Beam angle |
down 142° up 180° |
Colour rendering index (CRI) | 80 |
Photobiological safety according to EN 62471 | Risk group 1 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 Hz, 60 Hz |
Luminaires on B10A fuse | 17 |
Luminaires on B16A fuse | 27 |
Luminaires on C10A fuse | 28 |
Luminaires on C16A fuse | 45 |
Inrush current / Inrush current duration | 27 A / 250 µs |
CIE Flux Code / CEN Flux Code | 22 63 90 77 100 |
Type of protection | IP 65 |
Protection class | I |
Filament test | 650 °C |
Impact resistance | IK05 |
Ambient temperature for maintained power | -10 °C ... + 35 °C |
Conformity mark | CE |