Wall luminaire for escape route illumination. Housing: die-cast aluminium, powder-coated. With plastic lenses for area lighting. Driver integrated. For connection to the emergency power supply. With AC Control monitoring module for LUXIFAIR central battery units.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Luxifair AC-Control |
Battery | without |
Operating mode | maintained power mode |
Length L | 117 mm |
Width B | 190 mm |
Height H | 190 mm |
Weight | 1.9 kg |
Light source | LED |
Colour temperature | 6500 K |
Rated luminous flux, mains operation | 380 lm |
System power, mains operation | 4,9 W |
Rated luminous flux, emergency operation | 390 lm |
System power, emergency operation | 4,4 W |
System efficiency | 78 lm/W |
Glare evaluation UGR (4H 8H) | 40,6 |
Beam angle | 90°/60°/29°/60° |
Colour rendering index (CRI) | 70 |
Photobiological safety according to EN 62471 | Risk group 1 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 Hz, 60 Hz |
Luminaires on B10A fuse | 18 |
Luminaires on B16A fuse | 29 |
Luminaires on C10A fuse | 36 |
Luminaires on C16A fuse | 58 |
Inrush current / Inrush current duration | 3.3 A / 400 µs |
CIE Flux Code / CEN Flux Code | 39 66 86 96 100 |
Type of protection | IP 65 |
Protection class | I |
Filament test | 960°C - 30 seconds |
Impact resistance | IK07 |
Ambient temperature for maintained power | -10 °C ... + 40 °C |
Ambient temperature for non-maintained power mode | -10 °C ... + 40 °C |
Conformity mark | CE |