Decorative round surface-mounted luminaire. For escape route illumination. Base: metal, powder-coated. Diffuser made of non-yellowing plastic (PMMA), opal. Diffuser fastening: patented push system. Suitable for ceiling mounting, wall (surface). Driver integrated. For connection to the emergency power supply. With AC Control monitoring module for LUXIFAIR central battery units.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Luxifair AC-Control |
Battery | without |
Operating mode | Non-maintained power mode and maintained power mode |
Diameter D | 515 mm |
Height H | 98 mm |
Weight | 2.86 kg |
Light source | LED |
Colour temperature | 4000 K |
Rated luminous flux, mains operation | 2600 lm |
System power, mains operation | 24 W |
Rated luminous flux, emergency operation | 550 lm |
System power, emergency operation | 5,8 W |
System efficiency | 108 lm/W |
Glare evaluation UGR (4H 8H) | 18,3 |
Beam angle |
down 124° up 180° |
Colour rendering index (CRI) | 80 |
Colour tolerance | 4 SDCM |
Photobiological safety according to EN 62471 | Risk group 0 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 - 60 Hz |
Luminaires on B10A fuse | 10 |
Luminaires on B16A fuse | 17 |
Luminaires on C10A fuse | 18 |
Luminaires on C16A fuse | 29 |
Inrush current / Inrush current duration | 32 A / 250 µs |
CIE Flux Code / CEN Flux Code | 42 72 91 84 100 |
Type of protection | IP 40 |
Protection class | I |
Filament test | 650°C - 30 seconds |
Impact resistance | IK03 |
Ambient temperature for maintained power | -10 °C ... + 35 °C |
Ambient temperature for non-maintained power mode | -10 °C ... + 35 °C |
Conformity mark | CE , EAC |