Luminaire for escape route identification. Base: metal, powder-coated. Diffuser: plastic (PMMA), opal 4 plastic foils with escape route motifs included (ISO 7010). Can be converted into a suspended luminaire, via accessories.
Technical Specifications
Typ of emergency lighting | Self-contained system |
---|---|
Monitoring | Autotest |
Battery | NiMh |
Duration | 3 h |
Operating mode | maintained power mode |
Viewing Distance | 30 m |
Length L | 315 mm |
Width B | 315 mm |
Height H | 187 mm |
Weight | 2.78 kg |
Light source | LED |
Colour temperature | 6500 K |
System power, mains operation | 7,1 W |
Glare evaluation UGR (4H 8H) | 13,8 |
Colour rendering index (CRI) | 70 |
Photobiological safety according to EN 62471 | Risk group 0 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 50 - 60 Hz |
Luminaires on B10A fuse | 20 |
Luminaires on B16A fuse | 30 |
Luminaires on C10A fuse | 20 |
Luminaires on C16A fuse | 30 |
CIE Flux Code / CEN Flux Code | 39 69 89 79 100 |
Type of protection | IP 40 |
Protection class | I |
Filament test | 650°C - 30 seconds |
Impact resistance | IK03 |
Ambient temperature for maintained power | 5 °C ... + 25 °C |
Ambient temperature for non-maintained power mode | 5 °C ... + 40 °C |
Conformity mark | CE |