Ultra thin recessed downlight. For escape route illumination. Housing: die-cast aluminium, powder-coated. Lightguide and diffuser made of non-yellowing plastic (PMMA). Diffuser opal matt plastic. Ceiling installation with spring system. Including separate LED converter with connecting cable 250 mm. Compatible with DC, ideal for central battery systems. External driver with simple plug-in locking system.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Power circuit |
Battery | without |
Operating mode | maintained power mode |
Diameter D | 255 mm |
Height H | 3 mm |
Cut-out diameter DA | 234 mm |
Recess height HE | 35 mm |
Luminaire: recess height HEL | 31-51 mm |
Ceiling thickness S | 1-20 mm |
Weight | 0.81 kg |
Light source | LED |
Colour temperature | 3000 K |
Rated luminous flux, mains operation | 1650 lm |
System power, mains operation | 17 W |
Rated luminous flux, emergency operation | 1650 lm |
System power, emergency operation | 17 W |
System efficiency | 97 lm/W |
Glare evaluation UGR (4H 8H) | 26,6 |
Beam angle | 110° |
Colour rendering index (CRI) | 80 |
Photobiological safety according to EN 62471 | Risk group 0 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 - 60 Hz |
Luminaires on B10A fuse | 18 |
Luminaires on B16A fuse | 28 |
Inrush current / Inrush current duration | 15 A / 220 µs |
CIE Flux Code / CEN Flux Code | 48 79 96 100 100 |
Type of protection |
IP 54 on room side IP 20 |
Protection class | II |
Filament test | 650°C - 30 seconds |
Impact resistance | IK03 |
Ambient temperature for maintained power | -20 °C ... + 30 °C |
Ambient temperature for non-maintained power mode | -20 °C ... + 30 °C |
Conformity mark | CE , EAC |