Ultra thin recessed downlight. For escape route illumination. Housing: die-cast aluminium, powder-coated. Lightguide and diffuser made of non-yellowing plastic (PMMA). Diffuser opal matt plastic. Ceiling installation with spring system. Including separate LED converter with connecting cable 250 mm. Self-contained system with automatic self-test and feedback via DALI bus, only to RZB DALI monitoring system. External driver with simple plug-in locking system.
Technical Specifications
Typ of emergency lighting | Self-contained system |
---|---|
Monitoring | DALI-Sibe |
Battery | NiMh |
Duration | 3 h |
Operating mode | maintained power mode |
Diameter D | 190 mm |
Height H | 2 mm |
Cut-out diameter DA | 170 mm |
Recess height HE | 120 mm |
Luminaire: recess height HEL | 60-80 mm |
Ceiling thickness S | 1-20 mm |
Weight | 1.41 kg |
Light source | LED |
Colour temperature | 3000 K |
Rated luminous flux, mains operation | 780 lm |
System power, mains operation | 7,7 W |
Rated luminous flux, emergency operation | 350 lm |
System efficiency | 101 lm/W |
Glare evaluation UGR (4H 8H) | 26,4 |
Beam angle | 111° |
Colour rendering index (CRI) | 80 |
Photobiological safety according to EN 62471 | Risk group 0 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 50 - 60 Hz |
Luminaires on B10A fuse | 53 |
Luminaires on B16A fuse | 85 |
Luminaires on C10A fuse | 89 |
Luminaires on C16A fuse | 143 |
Inrush current / Inrush current duration | 30 A / 180 µs |
CIE Flux Code / CEN Flux Code | 47 79 96 100 100 |
Type of protection |
IP 54 on room side IP 20 |
Protection class | I |
Impact resistance | IK03 |
Ambient temperature for maintained power | 0 °C ... + 35 °C |
Ambient temperature for non-maintained power mode | 0 °C ... + 35 °C |
Conformity mark | CE , EAC |
Downloads
Light Calculator
The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.