Flat, square surface-mounted luminaire. Base: die-cast aluminium, powder-coated Cover: polycarbonate. With plastic lenses for escape route illumination. The converter is compatible with DC, making it ideal for central battery systems. Luminaires with limited surface temperature in accordance with EN 60598-2-24 for use in environments in which a deposit of conductive dust on the luminaire can be expected. Ball impact proof in accordance with DIN 18032-3. Qualified for use in the food and drink industry.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Power circuit |
Battery | without |
Operating mode | maintained power mode |
Length L | 198 mm |
Width B | 198 mm |
Height H | 38 mm |
Weight | 0.73 kg |
Light source | LED |
Colour temperature | 6500 K |
Rated luminous flux, mains operation | 450 lm |
System power, mains operation | 5,9 W |
Rated luminous flux, emergency operation | 440 lm |
System power, emergency operation | 5,6 W |
System efficiency | 76 lm/W |
Glare evaluation UGR (4H 8H) | 34,2 |
Beam angle | 144°/91° |
Colour rendering index (CRI) | 70 |
Photobiological safety according to EN 62471 | Risk group 2 |
Driver | Electronic ballast |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 Hz, 60 Hz |
Luminaires on B10A fuse | 18 |
Luminaires on B16A fuse | 29 |
Luminaires on C10A fuse | 36 |
Luminaires on C16A fuse | 58 |
Inrush current / Inrush current duration | 3.3 A / 400 µs |
CIE Flux Code / CEN Flux Code | 37 71 99 100 100 |
Type of protection | IP 65 |
Protection class | I |
Filament test | 850 °C |
Impact resistance | IK08 |
Ambient temperature for maintained power | -20 °C ... + 40 °C |
Ambient temperature for non-maintained power mode | -20 °C ... + 40 °C |
Safety marks | D-mark |
Conformity mark | CE |
Downloads
Light Calculator
The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.