Flat, square surface-mounted luminaire. Base: die-cast aluminium, powder-coated Cover: polycarbonate. With plastic lenses for area lighting. Driver integrated. For connection to the emergency power supply. With AC Control monitoring module for LUXIFAIR central battery units. Luminaires with limited surface temperature in accordance with EN 60598-2-24 for use in environments in which a deposit of conductive dust on the luminaire can be expected. Ball impact proof in accordance with DIN 18032-3. Qualified for use in the food and drink industry.
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Luxifair AC-Control |
Battery | without |
Operating mode | maintained power mode |
Length L | 198 mm |
Width B | 198 mm |
Height H | 38 mm |
Weight | 0.8 kg |
Light source | LED |
Colour temperature | 6500 K |
Rated luminous flux, mains operation | 490 lm |
System power, mains operation | 6,9 W |
Rated luminous flux, emergency operation | 490 lm |
System power, emergency operation | 6,6 W |
System efficiency | 71 lm/W |
Glare evaluation UGR (4H 8H) | 22,7 |
Beam angle | 117°/118° |
Colour rendering index (CRI) | 70 |
Photobiological safety according to EN 62471 | Risk group 2 |
Driver | Electronic ballast |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 Hz, 60 Hz |
Luminaires on B10A fuse | 18 |
Luminaires on B16A fuse | 29 |
Luminaires on C10A fuse | 36 |
Luminaires on C16A fuse | 58 |
Inrush current / Inrush current duration | 3.3 A / 400 µs |
CIE Flux Code / CEN Flux Code | 51 94 100 100 100 |
Type of protection | IP 65 |
Protection class | I |
Filament test | 850 °C |
Impact resistance | IK08 |
Ambient temperature for maintained power | -10 °C ... + 40 °C |
Ambient temperature for non-maintained power mode | -10 °C ... + 40 °C |
Safety marks | D-mark |
Conformity mark | CE |
Downloads
Light Calculator
The Online Light Calculator's purpose is a quick calculation and the results may not be perfectly accurate.