CENTRYXX D

672164.002

Wall luminaires, white

Luminaire for escape route identification. For signposting and illuminating of fire fighting equipment and call points and of first aid posts Base: die-cast aluminium, powder-coated Diffuser polycarbonate in prismatic shape. Legend both sides, in 90° angle arranged. Downward light emission with elliptical character. The converter is compatible with DC, making it ideal for central battery systems. Indicate required motif when placing your order! Luminaires with limited surface temperature in accordance with EN 60598-2-24 for use in environments in which a deposit of conductive dust on the luminaire can be expected.

Technical Specifications

Typ of emergency lighting Central battery system
Monitoring Power circuit
Battery without
Operating mode maintained power mode
Viewing Distance 24 m
Length L 199 mm
Width B 125 mm
Height H 199 mm
Weight 0.87 kg
Light source LED
Colour temperature 6500 K
System power, mains operation 8 W
System power, emergency operation 8 W
Glare evaluation UGR (4H 8H) 4,1
Colour rendering index (CRI) 70
Photobiological safety according to EN 62471 Risk group 1
Driver Converter
Control on/off
Voltage 220 - 240 V / 0 Hz, 50 Hz, 60 Hz
Luminaires on B10A fuse 31
Luminaires on B16A fuse 50
Luminaires on C10A fuse 52
Luminaires on C16A fuse 85
Inrush current / Inrush current duration 5 A / 50 µs
Type of protection IP 65
Protection class I
Filament test 850 °C
Impact resistance IK08
Ambient temperature for maintained power -20 °C ... + 40 °C
Ambient temperature for non-maintained power mode -20 °C ... + 40 °C
Safety marks D-mark
Conformity mark CE

Accessories

982274.002
Mounting set for through wiring surface installation