Luminaire for escape route identification. Housing: extruded aluminium profile, anodised or powder-coated. Display panel: highly transparent panel, plastic, with legend on one side/both sides. Driver integrated. For connection to the emergency power supply. With AC Control monitoring module for LUXIFAIR central battery units. Please indicate legend number when placing your order!
Technical Specifications
Typ of emergency lighting | Central battery system |
---|---|
Monitoring | Luxifair AC-Control |
Battery | without |
Operating mode | maintained power mode |
Viewing Distance | 14 m |
Length L | 233 mm |
Width B | 40 mm |
Height H | 184 mm |
Weight | 1.03 kg |
Light source | LED |
Colour temperature | 4000 K |
System power, mains operation | 4,7 W |
System power, emergency operation | 4,7 W |
Colour rendering index (CRI) | 80 |
Photobiological safety according to EN 62471 | Risk group 1 |
Driver | Converter |
Control | on/off |
Voltage | 220 - 240 V / 0 Hz, 50 - 60 Hz |
Luminaires on B10A fuse | 17 |
Luminaires on B16A fuse | 27 |
Luminaires on C10A fuse | 28 |
Luminaires on C16A fuse | 45 |
Inrush current / Inrush current duration | 27 A / 250 µs |
Type of protection | IP 40 |
Protection class | I |
Filament test | 650°C - 30 seconds |
Impact resistance | IK03 |
Ambient temperature for maintained power | 0 °C ... + 25 °C |
Ambient temperature for non-maintained power mode | 5 °C ... + 40 °C |
Conformity mark | CE |